You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 25 Next »

Too many power outages in Baker Lab, and other Chem buildings!

ChemIT's record of recent power outages

Date

Outage duration

Cause

Official link

ChemIT notes

2/27/2014
Thursday

2 minutes
CU's record: Per 3/3/14 email: On Thursday 2/27/14 at 9:50am the campus experienced a disruption of electricity.  The whole campus experienced an approximately 30 second outage.
Oliver's record: Power outage at 9:53a. Restored at 9:55a (more than one minute).

Procedural error?
Per 3/3/14 email: The outage was caused as a result of routine maintenance activities which were being conducted at the Campus' main substation which takes power from the NYSEG transmission system and provides it to campus.  This work has been conducted many times before without incident but in this case caused a major disruption of electricity supply.  Staff from Utilities and external technical resources are investigating the root cause of this unexpected event.

No link to info in 3/3/14 email?
Some delayed time-stamps, from the IT folks:
http://www.it.cornell.edu/services/alert.cfm?id=3072
Initial timing info, from the power folks:
http://www.cornell.edu/cuinfo/specialconditions/#2050

Michael led our effort to initially evaluate and restore systems, with Oliver adding to documentation and to-do's. Lulu completed the cluster restoration efforts.
Lost 1-2 hours each for Michael, Lulu, and Oliver.
Cornell called it a "power blip". In Oliver's books, any outage longer than seconds is not a "blip".
Q: Broke one GPU workstation?

1/27/2014
Monday

17-19 minutes
CU's record: Power outage at 2:22p. Restored around 2:41p.
Oliver's record: Power outage at 2:22p. Restored at 2:39p.

?

http://www.it.cornell.edu/services/alert.cfm?id=3040

Lulu, Michael, and Oliver shut down headnodes and other systems which were on UPS. (Those systems non UPS shut down hard, per usual.)
Lost 3 hours, for Lulu, Michael, and Oliver.
Roger away on vacation (out of the U.S.)

12/23/2013
Monday

2 minutes
CU's report: 08:36 AM - 8:38 AM
(ChemIT staff not in yet.)

Procedural error?

http://www.it.cornell.edu/services/alert.cfm?id=2982

Terrible timing, right before the longest staff holiday of the year.
ChemIT staff not present during failure.
Lost most of the day, for Roger and Oliver.
Michael Hint and Lulu way on vacation (out of the U.S.)

7/17/13

Half a morning (~2 hours)
CU's report: 8:45 AM - 10:45 AM

 

http://www.it.cornell.edu/services/alert.cfm?id=2711

 

Question: When power is initially restored, do you trust it? Or might it simply kick back off in some circumstances?

  • Because we don't know the answer to this question following any specific power outage, we are reluctant to turn back on servers right away. Instead, we like to wait ~10-25 minutes.

What would it cost to UPS our research systems?

Assuming protection for 1-3 minutes MAXIMUM:

Do all headnodes and stand-alone computers in 248 Baker Lab

  • Started getting done. About $170/ headnode every ~4 years.

CCB Headnodes' UPS status:

Cluster

Done

Not done

Notes

Collum

X
Spring'14

 


Lancaster, with Crane (new)

X
Spring'14

 

Funded by Crane.

Hoffmann

X
Spring'14

 

 

Scheraga

X
Fall'14

 

See below chart for s4 tand-alone computational computers

Loring

 

X

Unique: Need to do ASAP

Abruna

 

X

Unique: Need to do ASAP

C4 Headnode: pilot
Widom's 2 nodes there.

X
Old UPS

 

Provisioned on the margin, since still a pilot.
(Not funded by Widom.)

Widom

 

X

See "C4", above

Stand-alone computers' UPS status:

Computer

Done

Note done

Notes

Scheraga's 4 GPU rack-mounted computational computers

 

X

Need to protect?
Data point: Feb'14 outage resulted in one of these not booting up correctly.

NMR web-based scheduler

X
Spring'14

 

 

Coates: MS SQL Server

 

X

Unique: Need to do ASAP

Do all switches: Maybe ~$340 ($170*2), every ~4 years.

  • Recommend: Do ASAP.
  • Q: Funding?
  • Other issues and concerns with actually implementing this approach:
    • Rack space. Maybe power. Maybe cord lengths. What other issues?

Do all compute nodes: ~$18K every  ~4 years.

  • ~20 20amp UPS's ($900 each) required.
  • Estimates are simply back-of-the-envelope calculations.
  • If were to actually implement, there may be smarter ways to do this, but the total cost will likely not be lower.
    • In fact, costs may be higher, if sufficiently higher benefit doing it a different way, for example.
  • Issues and concerns with actually implementing this approach:
    • Costs. Rack space. Maybe power. Maybe cord lengths. What other issues?

Compute node counts, for UPS pricing estimates. Does not include head node:

Cluster

Compute node count

Power strip equivalents
(~8/strip MAX)

Cost estimate,
every 4 years

Notes

Collum

8?

1

$900


Lancaster, with Crane (new)

12?

2

$1.8K


Hoffmann

14?

2

$1.8K

 

Scheraga

92?

13

$11.7K


Loring

6?

1

$900


Abruna

6?

1

$900


C4 Headnode: pilot
Widom's 2 nodes there.

N/A

N/A

N/A

This CCB Community headnode pilot has no compute nodes of its own.

Widom

2

1

?

Compute nodes are hanging off of "C4", above.

TOTALS

~140?

21

$18K + Widom

 

Procedures and reminders

Reboot switches?

  • 8 switches support the clusters (out of 12 in the room).

Start headnodes, if not on already

  • Only a few are on UPS. Those can obviously be left on.
  • None should be set to auto-start on power-off.

Confirm headnodes accessible via SSH

PuTTY on Windows

Use FMPro to get connection info?! (not the right info there, though...)

Menu => List Machine / User Selections = > List Group or selected criteria

  • Machine function => Server HN

Start compute nodes

If nodes done show up, consider:

  • Restart Torque scheduler on problematic nodes.
  • Try rebooting the switch the affected nodes are connected to, especially if the problematic nodes are grouped to a single switch.
  • Hook up a monitor as one of the high nodes boot.
  • No labels