Initial Research:
In order to help us develop our clear well design, we conducted extensive literature and online research on granular filtration and backwash. We found Surface Water Treatment for Communities in Developing Countries by Christopher R. Schulz and Daniel A. Okun and Physicochemcial Processes for Water Quality Control by Walter J. Weber, Jr. to be useful sources of information in our research. These two documents are the only sources of information but there are solely mentioned because they essentially contain the same information as other objects of our online and literature review.
From Christopher R. Schulz and Daniel A. Okun, we learned the following useful information with regards to filtration:
• Filtration is the separation of suspended impurities from water by passage through porous media.
• Slow sand filtration consists of slowly filtering water through a layer of ungraded fine sand. Periodically, the top layer is clogged by impurities and is skimmed off the top.
• Rapid sand filtration rapidly conducts filtration in depth as compared to the slow sand filter which uses only the top layer to capture suspended particles. A lighter anthracite coal layer with larger pore spaces than sand is used on top of a sand layer to capture larger particles while allowing the smaller particles passage to be captured by the lower sand layer.(Schulz et. al 146)
• Backwashing is the act of removing the captured impurities in the filter bed by introducing enough water, usually from the effluent end, to fluidize and expand the bed and wash away the now released impurities. Backwashing is an art. There is neither a set time nor a set amount of backwash water required. If a filter is heavily clogged, significant length of backwash and greater backwash water for greater bed expansion are required. If the influent water is relatively low in NTU, less clogging may occur and a shorter backwash and less water may be required. Consequently, rapid filtration and required backwash operations necessitate a well trained crew of operators. This finding leads us to define our objective as not only providing a clear well design that works but a set of instructions in operating that design.(Schulz et. al 159)
• Headloss via expanded media can be calculated as below:

INPUT MATHTYPE Equation for 8.1 .(Schulz et. al 161)
From Walter J. Weber, Jr., we learned the following useful information with regards to filtration.
• INPUT MATHTYPE Equation 4-48 Pressure drop across Fluidized bed,
As the rate of backwash flow is increased, there is a linear increase in pressure drop to the point where some movement or reorientation of the granules takes places. At a slighter higher rate, the bed becomes fluidized and the pressure drop remains constant.
• INPUT MATHTYPE Equation 4-49 Minimal Fluidization Velocity (Weber 172)
• INPUT MATHTYPE Equation 4-50 to 4-53. Fluidization Velocity to achieve different degrees of expansion.(Weber 173)