Linear Flow Orifice Meter Design for 1000 L/min Flow Rate and 10 rows

The LFOM design with the eaiest construction has an initial H.flowloc = 1.5cm, and Pi.Lfomorifice = 10

This is a visual representation of the Riser pipe

This is the tabular form of the design

  • The diameter is equal to 1.905 cm

    Row

    Height, cm

    Number of orifices

    0

    0

    13

    1

    2

    9

    2

    4

    8

    3

    6

    5

    4

    8

    5

    5

    10

    4

    6

    12

    4

    7

    14

    4

    8

    16

    3

    9

    18

    3

    10

    20

    3