Alum Dosing

Alum Dose

Alum dosing has been an important variable throughout flocculation history. It is considered an art form and is generally picked up through practice and experience. At the Cornell Water treatment plant the operators rely on past data and a streaming current director to establish their alum dosing. They also rely on some rules of thumb that are affected by the temperature and the turbidity of the water. It appears that the higher the temperature the less alum is needed. This data is displayed in Table 1.
Table 1. Rule of thumb data used by Cornell University's Water Treatment Plant Operators.

 

Temperature > 10°C

Temperature < 10°C

NTU

Alum dose (mg/L)

Alum dose (mg/L)

1

17

10

10

27

20

50

43

34

100

60

46

200

77

60

In an attempt to automate and decrease the mystery behind alum dosing the log relationship equation (Y = A + B*log(NTU)) was used to test its impact on flocculation in the pilot plant flocculator. After the value of A was lowered and the tube settlers stopped clogging there appeared to be good floc formation and clean water being produced in the flocculator. While the third section appeared to break floc ups the alum dosing was sufficient so that by the end of the second section the turbidity was usually around 1 NTU and was almost always below 2 NTU (see Figure 12 and Figure 18). The raw water turbidity coming into the flocculator stayed between 2 and 6 NTU during most tests that were run. While the turbidity is low equation 18 allows good floc formation and for clean water to be produced by AguaClara technology.
Alum dosing was also investigated by watching floc formation in the flocculator at different alum doses. This was done in an attempt to note if it was possible to visually discern when the alum dose needed to be changed. Doses of 0, 5, 20, and 50 mg/L were noted.
Upon observing 0 alum dose, it was very clear that there wasn't any improvement through the tank. In fact the whole way through the flocculator it looked as though there were tiny particles floating along with big particles and this never changed.
When observing 5 mg/L the difference was hard to discern. It appeared that there was improvement through the tank. The last two sections didn't appear to have as many small particles in between some of the larger particles were but the flocs that were seen appeared to be smaller than those observed when using equation 18.
When I raised the alum dose to 20 at first there appeared to be a rush of floc at the beginning that moved up the first section of the tank. It is not clear if this was due to the introduction of the higher alum dose or not. After the initial rush of flocs the water entering the tank didn't seem as dirty as the raw water entering the tank without any alum. The floc formation appears earlier in the tank, after about a third of the first section. They are still small at this point but the improvement over the end of the first section and the middle of the second section is rapid. Most of the particles are in floc and there are not as many particles in between flocs.
When I finally increased the dose to 50 mg/L the water in the first section appeared to have the same small particles in between larger particles as the raw water when there was no alum added.. Through the tank it appeared that there lots of medium to small sized flocs, almost as though there were more medium sized flocs and not any large flocs. It does not look like the flocs are large. They are small and never get bigger throughout the tank. There are a few rare flocs that could be considered large. This is contrary to what I had expected to see, I thought I would see the same type of floc as when the tube settlers were clogging. It appeared almost as though by overdoing it negated the effect of the alum, by creating the reverse charge on the particles which again had a repelling affect.

Alum Dose

For the majority of testing, alum dose was set by equation 18. After the change of A from 15 to 10 was made this approach was effective for the low turbidities that the flocculator experienced this summer. Hopefully in the future the raw water turbidity will change enabling testing of higher turbidities. Through use of equation 18, observing the floc tank and conversations with the operators at the water treatment plant it has become apparent that there is still a lot of research that needs to be done regarding alum dose. Observing the floc tank was helpful in being able to identify different kinds of floc and what different alum doses looked like in the water entering the water treatment plant. The water treatment plant has now switched to a different coagulant but if they had to go back to alum they said they would use past experience and alum doses as well as jar tests to set their doses. This suggests that for each water treatment plant an equation, formula or at least a rule of thumb could be developed off of past water treatment for future dosing. If this formula would be translatable to other water treatment plants and different water types is uncertain. The run increment alum dose test should help to shed light on alum dosing as it allows the alum dose to be changed while at a relatively constant raw water turbidity. Hopefully the data from this test will show either an optimum dose or a small range of optimal doses for specific settled water turbidity.

Optimal Alum Dose Testing

Because the pilot plant takes water directly from the stream, environmental conditions change all the time and affect the incoming turbidity to the plant as well as the chemical composition of the particles causing turbidity. It is therefore necessary to determine the best alum dose for each day of testing to ensure the formation of good flocs. This requirement was implemented in the following way:
The Process Controller was used under the "Increment Alum" setting, which starts the Alum Dose at 0 mg/L, and increments at 5 mg/L until it reaches a maximum of 40 mg/L. Each of the alum doses ran for a 30-minute period, or for about 3 times the residence time of the tank. After the completion of the test, data processing was performed to select the data from the last 10 minutes of each individual alum increment. The first 20 minutes of data were rejected because the residence time in the flocculator was 10 minutes, and the residence time in the tube settler was also about 10 minutes. Therefore, in order to get readings from the final turbidimeter that were representative of the alum dose that we were testing, we discarded the first 20 minutes of data at each alum dose. The outgoing turbidity (from turbidimeter 4) was then analyzed for each increment, and the alum dose achieving the lowest turbidity was selected for the second part of the experiment.