Topic or eventAction takenAction requiredNotes
ChemIT UPS in cluster rack died. Would not turn on.

Moved Widom HeadNode to Loring UPS

Moved C4 to Loring UPS

Moved switch (Collum+Widom) to Collum UPS (Lulu add)

Removed ChemIT UPS and plugged in to charge, just in case.

  
ChemIT UPS for Windows servers – limited battery power, Hyper-V machines were not able to shut down gracefully.Even after 24 hours charging, Synology shows it with only 672 seconds of battery life. Probably not even thatNeeds battery or replacement 
Schernology (Scheraga's Synology) could not be accessed to cleanly shut down since network not working.Lulu did push power button to shutdown system. It should go to safe mode when battery goes to low. Could have let UPS shut it down cleanly if wanted to wait (confirm true?)Lulu investigating options. 
Mathematica license server did not start after restart.Restarted manually. (common issue)  
NMR Web server didn't start up right.Needed to be kicked a bit to start.This Gateway needs to go. 
NMR Router pukedReprogrammed passwords and forwarding for SSH & RDP.Needs external administration access configured. 

...