Summer 2013 and winter 2014, there were an inordinate number of power outages in Baker Lab, and other Chem buildings!

See also

...

Date

...

Outage duration

...

Cause

...

Official link

...

ChemIT notes

...

2/27/2014
Thursday

...

Question

...

?

...

Some delayed time-stamps, from the IT folks:
http://www.it.cornell.edu/services/alert.cfm?id=3072
Initial timing info, from the power folks:
http://www.cornell.edu/cuinfo/specialconditions/#2050

...

Michael led our effort to initially evaluate and restore systems, with Oliver adding to documentation and to-do's. Lulu completed the cluster restoration efforts.
Lost 1-2 hours each for Michael, Lulu, and Oliver.
Cornell called it a "power blip". In Oliver's books, any outage longer than seconds is not a "blip".
Q: Broke one GPU workstation?

...

1/27/2014
Monday

...

17-19 minutes
CU's record: Power outage at 2:22p. Restored around 2:41p.
Oliver's record: Power outage at 2:22p. Restored at 2:39p.

...

?

...

http://www.it.cornell.edu/services/alert.cfm?id=3040

...

Lulu, Michael, and Oliver shut down headnodes and other systems which were on UPS. (Those systems non UPS shut down hard, per usual.)
Lost 3 hours, for Lulu, Michael, and Oliver.
Roger away on vacation (out of the U.S.)

...

12/23/2013
Monday

...

2 minutes
CU's report: 08:36 AM - 8:38 AM
(ChemIT staff not in yet.)

...

Human error?

...

http://www.it.cornell.edu/services/alert.cfm?id=2982

...

Terrible timing, right before the longest staff holiday of the year.
ChemIT staff not present during failure.
Lost most of the day, for Roger and Oliver.
Michael Hint and Lulu way on vacation (out of the U.S.)

...

7/17/13

...

Half a morning (~2 hours)
CU's report: 8:45 AM - 10:45 AM

...

 

...

http://www.it.cornell.edu/services/alert.cfm?id=2711

...

 

Question: When power is initially restored, do you trust it? Or might it simply kick back off in some circumstances?

  • Because we don't know the answer to this question following any specific power outage, we are reluctant to turn back on servers right away. Instead, we like to wait ~10-25 minutes.

What would it cost to UPS our research systems?

Assuming protection for 1-3 minutes MAXIMUM:

Do all headnodes and stand-alone computers in 248 Baker Lab

  • Started getting done. About $170/ headnode every ~4 years.

CCB Headnodes' UPS status:

...

Cluster

...

Done

...

Not done

...

Notes

...

Collum

...

X
Spring'14

...

 

...

Lancaster, with Crane (new)

...

X
Spring'14

...

 

...

Funded by Crane.

...

Hoffmann

...

X
Spring'14

...

 

...

 

...

Scheraga

...

X
Fall'14

...

 

...

See below chart for s4 tand-alone computational computers

...

Loring

...

 

...

X

...

Unique: Need to do ASAP

...

Abruna

...

 

...

X

...

Unique: Need to do ASAP

...

C4 Headnode: pilot
Widom's 2 nodes there.

...

X
Old UPS

...

 

...

Provisioned on the margin, since still a pilot.
(Not funded by Widom.)

...

Widom

...

 

...

X

...

See "C4", above

 

...

Also consider

  • When communicate with others, and what gets communicated, for what purpose?

Stand-alone computers' UPS status:

Computer

Done

Note done

Notes

Scheraga's 4 GPU rack-mounted computational computers

 

X

Need to protect?
Data point: Feb'14 outage resulted in one of these not booting up correctly.

NMR web-based scheduler

X
Spring'14

 

 

Coates: MS SQL Server

 

X

Unique: Need to do ASAP

Do all switches: Maybe ~$340 ($170*2), every ~4 years.

  • Recommend: Do ASAP.
  • Q: Funding?
  • Other issues and concerns with actually implementing this approach: Rack space. Maybe power. Maybe cord lengths. What other issues?

Do all compute nodes: ~$18K every  ~4 years.

  • ~20 20amp UPS's ($900 each) required.
  • These are from back-of-the-envelope calculations.
  • If were to actually implement, may be smarter ways to do this, but cost will likely not be lower. (In fact, costs may be higher, if sufficiently higher benefit doing it a different way, for example.
  • Issues and concerns with actually implementing this approach: Costs. Rack space. Maybe power. Maybe cord lengths. What other issues?

Compute node counts, for UPS pricing estimates. Does not include head node:

Cluster

Compute node count

Cost estimate

Notes

Collum

8?

 

Sprin

Lancaster, with Crane (new)

12?

 

Funded by Crane.

Hoffmann

14?

 

 

Scheraga

92?

 

See below chart for s4 tand-alone computational computers

Loring

6?

X

Unique: Need to do ASAP

Abruna

6?

X

Unique: Need to do ASAP

C4 Headnode: pilot
Widom's 2 nodes there.

N/A

 

This CCB Community headnode pilot is provisioned on the margin.
(Not funded by Widom.)

Widom

2

X

See "C4", above

Procedures and reminders

Reboot switches?

  • 8 switches support the clusters (out of 12 in the room).

Start

...

head nodes, if not on already

  • Only a few are on UPS. Those can obviously be left on.
  • None should be set to auto-start on power-off.

Confirm

...

head nodes accessible via SSH

PuTTY on Windows

Use FMPro to get connection info?! (not the right info there, though...)

Menu => List Machine / User Selections = > List Group or selected criteria

  • Machine function => Server HN

Start compute nodes

If nodes done show up, consider:

...