Method

Gtheta Value for k-e realizable 1_5 W one baffle

Ave of Cell's Product (1)

.6698

Ave G* Floc residence time (2)

45

Ave G*Ave N (3)

.617


Wiki MarkupGtheta was also plotted using the custom function in FLUENT.

Wiki Markup

\\  !GthetaaGtheta plot.png|width=713,height=412!
   GӨ = \[ε/υ\]^1/2^ \* \[Cell Volume/Vol. flow rate{~}cell~/Cell Volume\]       (4)
\\
\\ The Gtheta plot values range from 0 to 3000, and the highest values are concentrated at the separation regime.
\\

 Conclusion

The Gtheta that compares best to mechanically mixed floculators is the Gtheta calculated from method 2, where the G value is averaged, and this averaged value is multiplied by the residence time of a particle. As suggested in discussions with Monroe, this simplistic definition fails to incorporate the weighted flow average.

...