According to the results of the third experiment, the [third experiment|https://confluence.cornell.edu/display/AGUACLARA/Experiment+3+Repeated+Lime+Input+to+Overload+Reactor] the team discussed that the best way to achieve the saturation pH value in a longer period of time was by reducing the flow rate. Flow rate reduction will imply a reduction in the up flow velocity and will allow a longer retention time in the reactor. To probe this hypothesis, the team continued with the idea of increasing the volume of the lime in the reactor in order to provide more solid lime surface area, repeating the conditions of the the third experiment but reducing the amount of lime to 100g and changing the flow rate to 30mL/min.
Procedure

100 grams of lime was mixed with tap water and stirred to form a slurry. This was fed through the vertical column. The flow rate was 30ml/min in both apparatuses. All the other procedures were the same as described on materials and methods.

...

The second half of the experiment corresponds to a new addition of 100 grams of lime after 45 hours. Low readings are due to pH probe calibration. It can be observed that the increase in pH was dramatic and that both reactors remained above 12 for 19 hours (A1) and 27.5 hours (A2). Despite these promising results, the high fluctuation and the readings above 12.6 make them inaccurate and nullify the data. It is necessary to repeat the experiment when there is more certainty regarding the pH probe readings.